{"id":1668,"date":"2021-12-28T08:50:17","date_gmt":"2021-12-28T08:50:17","guid":{"rendered":"https:\/\/zecovalve.com\/spotlight-back-seating-on-api600-wedge-gate-valves-zeco.html"},"modified":"2022-10-17T12:57:43","modified_gmt":"2022-10-17T12:57:43","slug":"spotlight-back-seating-on-api600-wedge-gate-valves-zeco","status":"publish","type":"post","link":"https:\/\/zecovalve.com\/fr\/spotlight-back-seating-on-api600-wedge-gate-valves-zeco.html","title":{"rendered":"Test de si\u00e8ge arri\u00e8re de vanne \u00e0 vanne - Si\u00e8ge arri\u00e8re d&#039;une vanne"},"content":{"rendered":"<h2 class=\"wp-block-heading\" id=\"h-what-is-a-backseat\">Qu&#039;est-ce qu&#039;une banquette arri\u00e8re ?<\/h2>\n\n\n\n<p>Une banquette arri\u00e8re est un agencement de si\u00e8ges \u00e0 l\u2019int\u00e9rieur du capot. <\/p>\n\n\n\n<p>Il assure l&#039;\u00e9tanch\u00e9it\u00e9 entre la tige et le chapeau et emp\u00eache la pression du syst\u00e8me de s&#039;accumuler contre la garniture de la vanne lorsque la vanne est compl\u00e8tement ouverte. Les si\u00e8ges arri\u00e8re sont souvent utilis\u00e9s dans les vannes \u00e0 vanne et \u00e0 soupape.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\" id=\"h-valve-backseat-test-pressure\">Pression d&#039;essai du si\u00e8ge arri\u00e8re de la valve<\/h2>\n\n\n\n<p>La pression d&#039;essai ne doit pas \u00eatre inf\u00e9rieure \u00e0 la pression maximale admissible 110% \u00e0 38 \u00b0C (100 \u00b0F). Par exemple, si vous disposez d&#039;une valve de 900 Ib, 20 pouces avec A216 Gr. Mat\u00e9riau WCB, votre MAP sera de 2 252 psi (conform\u00e9ment au tableau 2-1.1 ASME B16.34). Le 110 % de cette valeur sera de 2477 psi. La pression d&#039;essai de votre banquette arri\u00e8re sera donc de 2 477 psi.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\" id=\"h-backseat-test-duration\">Dur\u00e9e du test sur la banquette arri\u00e8re<\/h2>\n\n\n\n<p>La dur\u00e9e du test de vanne d\u00e9pend de la taille de la vanne selon la norme API 598. La dur\u00e9e du test est de 15 secondes pour les vannes de moins de 2 pouces, de 60 secondes pour les vannes de plus de 2 pouces.<\/p>\n\n\n\n<p>Le presse-\u00e9toupe de la vanne doit \u00eatre soigneusement inspect\u00e9 lorsqu&#039;il est soumis \u00e0 la pression d&#039;essai du si\u00e8ge arri\u00e8re. Semblable au test de coque de valve, aucune fuite n&#039;est acceptable pour le test de si\u00e8ge arri\u00e8re.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\" id=\"h-why-valves-need-backseat\">Pourquoi les vannes ont-elles besoin d&#039;un si\u00e8ge arri\u00e8re\u00a0?<\/h2>\n\n\n\n<p>A l&#039;ouverture, l&#039;emballage est soumis \u00e0 une pression de service. S&#039;il existe une structure de si\u00e8ge arri\u00e8re, il est possible d&#039;emp\u00eacher la pression du fluide de travail d&#039;agir sur la garniture d&#039;\u00e9tanch\u00e9it\u00e9 et la dur\u00e9e de vie de la garniture d&#039;\u00e9tanch\u00e9it\u00e9 peut \u00eatre prolong\u00e9e afin que la vanne ne pr\u00e9sente pas de fuite externe.<\/p>\n\n\n\n<p>Une autre fonction est qu&#039;en cas de fuite au niveau de la garniture d&#039;\u00e9tanch\u00e9it\u00e9, la vanne peut \u00eatre compl\u00e8tement ouverte pour sceller la partie d&#039;\u00e9tanch\u00e9it\u00e9 sup\u00e9rieure de sorte que le presse-\u00e9toupe ou le manchon de garniture puisse \u00eatre desserr\u00e9 pour remplacer la garniture. Par cons\u00e9quent, le dispositif d\u2019\u00e9tanch\u00e9it\u00e9 sup\u00e9rieur est requis pour le robinet-vanne, le robinet \u00e0 soupape et le papillon des gaz.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\" id=\"h-if-the-backseat-doesn-t-leak-during-the-test-then-is-it-acceptable-to-re-pack-a-valve-on-the-back-seat\">Si la banquette arri\u00e8re ne fuit pas pendant le test, est-il alors acceptable de r\u00e9installer une valve sur la banquette arri\u00e8re\u00a0?<\/h2>\n\n\n\n<p>Les tests sur la banquette arri\u00e8re se font uniquement avec de l&#039;eau \u00e0 temp\u00e9rature ambiante. Cela ne d\u00e9montre pas l&#039;\u00e9tanch\u00e9it\u00e9 pour tous les services dans lesquels la vanne pourrait \u00eatre utilis\u00e9e, c&#039;est-\u00e0-dire un service \u00e0 haute temp\u00e9rature, des gaz dangereux ou toxiques, etc.<\/p>\n\n\n\n<p>Un certain nombre de normes API contiennent un langage qui met en garde contre l\u2019utilisation aveugle de la banquette arri\u00e8re. Toutes les normes n&#039;ont pas la m\u00eame<br>le langage est indiqu\u00e9 ci-dessous (c&#039;est-\u00e0-dire API 6D), mais le message ici est clair.<\/p>\n\n\n\n<p>API 600, \u00ab\u00a0Steel Gate Valves and Butt-welding Ends, Bolted Bonnets\u00a0\u00bb, section 5.8.9, indique \u00ab\u00a0Une disposition de si\u00e8ge arri\u00e8re est une exigence pour toutes les vannes et robinets \u00e0 soupape et, en tant que telle, n&#039;est pas cens\u00e9e impliquer une recommandation du fabricant. pour son utilisation dans le but d\u2019ajouter ou de remplacer une garniture lorsque la vanne est sous pression \u00bb.<\/p>\n\n\n\n<p>La section 6.2.3 de l&#039;API 589, \u00ab\u00a0Inspection et test des vannes\u00a0\u00bb, indique que\u00a0\u00ab\u00a0la r\u00e9ussite du test de la banquette arri\u00e8re ne doit pas \u00eatre interpr\u00e9t\u00e9e comme une recommandation.<br>par le fabricant de la vanne que, pendant que la vanne est sous pression, la vanne peut \u00eatre remball\u00e9e ou la garniture peut \u00eatre remplac\u00e9e.<\/p>\n\n\n\n<p>La vanne ZECO est une bonne <a href=\"https:\/\/zecovalve.com\/fr\/produit\/12-inch-gate-valve\/\" data-internallinksmanager029f6b8e52c=\"6\" title=\"Fournisseur de robinet-vanne de 12 pouces\" target=\"_blank\" rel=\"noopener\">Fournisseur de robinet-vanne de 12 pouces<\/a>, si vous recherchez un <a href=\"https:\/\/zecovalve.com\/fr\/produit\/manual-gate-valve\/\" data-internallinksmanager029f6b8e52c=\"5\" title=\"Fabricant de vannes \u00e0 commande manuelle\" target=\"_blank\" rel=\"noopener\">Fabricant de vannes \u00e0 commande manuelle<\/a>, n&#039;h\u00e9sitez pas \u00e0 nous contacter.<\/p>\n\n\n\n<!-- Andy:h-related-tags -->\n<h2 id=\"h-related-tags\">Balises associ\u00e9es :<\/h2>\n<!-- \/Andy:h-related-tags -->\n\n\n\n<div class=\"re_main\">\n<a href=\"https:\/\/zecovalve.com\/fr\/\">Soupape ZECO<\/a>\n\n<\/div>\n\n\n\n<div class=\"re_main\">\n<a href=\"https:\/\/zecovalve.com\/fr\/categorie-de-produits\/globe-valve\/\">Fabricant de robinets \u00e0 soupape \u2013 Diff\u00e9rents types de robinets \u00e0 soupape<\/a>\n\n<\/div>\n\n\n\n<div class=\"re_main\">\n<a href=\"https:\/\/zecovalve.com\/fr\/categorie-de-produits\/gate-valve\/\">Fabricant de robinets-vannes \u2013 Diff\u00e9rents types de robinets-vannes<\/a>\n\n<\/div>\n\n\n\n<div class=\"re_main\">\n<a href=\"https:\/\/zecovalve.com\/fr\/china-gate-valves-suppliersnon-rising-stem-gate-valvesks-gate-valves.html\/\">Qu'est-ce qu'un robinet-vanne ?<\/a>\n\n<\/div>\n\n\n\n<div class=\"re_main\">\n<a href=\"https:\/\/zecovalve.com\/fr\/the-function-of-globe-valve-in-pipeline-system.html\/\">Que sont les vannes \u00e0 soupape\u00a0?<\/a>\n\n<\/div>\n\n\n\n<div class=\"re_main\">\n<a href=\"https:\/\/zecovalve.com\/fr\/advantages-and-disadvantages-of-globe-valves.html\/\">Qu'est-ce qu'un robinet \u00e0 soupape ?<\/a>\n\n<\/div>\n\n\n\n<div class=\"re_main\">\n<a href=\"https:\/\/zecovalve.com\/fr\/gate-valve-problems.html\/\">R\u00e9paration de vannes \u00e0 vanne<\/a>\n\n<\/div>\n\n\n\n<p>Dix articles avant et apr\u00e8s<\/p>\n\n\n\n<p><a href=\"https:\/\/zecovalve.com\/fr\/fugitive-emission-zeco.html\/\">\u00c9MISSION FUGITIVE | Zeco<\/a><\/p>\n\n\n\n<p><a href=\"https:\/\/zecovalve.com\/fr\/ansi-b16-valve-face-to-face-dimensions-zeco.html\/\">Dimensions face \u00e0 face de la vanne ANSI B16 | Zeco<\/a><\/p>\n\n\n\n<p><a href=\"https:\/\/zecovalve.com\/fr\/zeco-flowturn-sight-glass-and-flow-indicator-ex-stock-zeco.html\/\">Voyant Zeco-Flowturn et indicateur de d\u00e9bit en stock | Zeco<\/a><\/p>\n\n\n\n<p><a href=\"https:\/\/zecovalve.com\/fr\/a-contentious-issue-zeco.html\/\">UNE QUESTION CONTENTIELLE | Zeco<\/a><\/p>\n\n\n\n<p><a href=\"https:\/\/zecovalve.com\/fr\/improve-total-cost-of-ownership-with-valves-zeco.html\/\">Am\u00e9liorez le co\u00fbt total de possession gr\u00e2ce aux vannes | Zeco<\/a><\/p>\n\n\n\n<p><a href=\"https:\/\/zecovalve.com\/fr\/proven-design-superior-quality-price-and-delivery-zeco.html\/\">Conception \u00e9prouv\u00e9e, qualit\u00e9, prix et livraison sup\u00e9rieurs | Zeco<\/a><\/p>\n\n\n\n<p><a href=\"https:\/\/zecovalve.com\/fr\/double-block-and-bleed-valves-dual-valve-zeco.html\/\">VANNES DOUBLE BLOCAGE ET PURGE \u2013 DOUBLE VANNE | Zeco<\/a><\/p>\n\n\n\n<p><a href=\"https:\/\/zecovalve.com\/fr\/compact-quad-rack-pinnion-actuator-zeco.html\/\">Actionneur compact \u00e0 quatre cr\u00e9maill\u00e8res et pignons | Zeco<\/a><\/p>\n\n\n\n<p><a href=\"https:\/\/zecovalve.com\/fr\/slfsbv01-floating-ball-valve-150-to-600-class-zeco.html\/\">SLFSBV01 Robinet \u00e0 tournant sph\u00e9rique flottant Classe 150 \u00e0 600 | Zeco<\/a><\/p>\n\n\n\n<p><a href=\"https:\/\/zecovalve.com\/fr\/valve-test-standards-zeco.html\/\">NORMES D&#039;ESSAI DES VANNES | Zeco<\/a><\/p>","protected":false},"excerpt":{"rendered":"<p>Qu&#039;est-ce qu&#039;une banquette arri\u00e8re ? Une banquette arri\u00e8re est un agencement de si\u00e8ges \u00e0 l\u2019int\u00e9rieur du capot. Il assure l\u2019\u00e9tanch\u00e9it\u00e9 entre la tige et le chapeau\u2026 <a title=\"Test de si\u00e8ge arri\u00e8re de vanne \u00e0 vanne - Si\u00e8ge arri\u00e8re d&#039;une vanne\" class=\"read-more\" href=\"https:\/\/zecovalve.com\/fr\/spotlight-back-seating-on-api600-wedge-gate-valves-zeco.html\" aria-label=\"Plus sur Gate Valve Backseat Test \u2013 Backsitting A Valve\">Lire plus<\/a><\/p>","protected":false},"author":2,"featured_media":16097,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_generate-full-width-content":"","kt_blocks_editor_width":"","footnotes":""},"categories":[1],"tags":[3371,3369,3370],"class_list":["post-1668","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-uncategorized","tag-backseat-valve-drain","tag-backseating-a-valve","tag-gate-valve-backseat-test","generate-columns","tablet-grid-50","mobile-grid-100","grid-parent","grid-50"],"featured_image_src_large":["https:\/\/zecovalve.com\/wp-content\/uploads\/2022\/06\/wedge-gate-valve-4.jpg",800,600,false],"author_info":{"display_name":"Jerry","author_link":"https:\/\/zecovalve.com\/fr\/author\/jerry"},"comment_info":0,"category_info":[{"term_id":1,"name":"Uncategorized","slug":"uncategorized","term_group":0,"term_taxonomy_id":1,"taxonomy":"category","description":"","parent":0,"count":452,"filter":"raw","cat_ID":1,"category_count":452,"category_description":"","cat_name":"Uncategorized","category_nicename":"uncategorized","category_parent":0}],"tag_info":[{"term_id":3371,"name":"backseat valve drain","slug":"backseat-valve-drain","term_group":0,"term_taxonomy_id":3371,"taxonomy":"post_tag","description":"","parent":0,"count":1,"filter":"raw"},{"term_id":3369,"name":"backseating a valve","slug":"backseating-a-valve","term_group":0,"term_taxonomy_id":3369,"taxonomy":"post_tag","description":"","parent":0,"count":1,"filter":"raw"},{"term_id":3370,"name":"gate valve backseat test","slug":"gate-valve-backseat-test","term_group":0,"term_taxonomy_id":3370,"taxonomy":"post_tag","description":"","parent":0,"count":1,"filter":"raw"}],"taxonomy_info":{"category":[{"value":1,"label":"Uncategorized"}],"post_tag":[{"value":3371,"label":"backseat valve drain"},{"value":3369,"label":"backseating a valve"},{"value":3370,"label":"gate valve backseat test"}]},"yoast_head":"<!-- This site is optimized with the Yoast SEO Premium plugin v15.4 - https:\/\/yoast.com\/wordpress\/plugins\/seo\/ -->\n<title>Gate Valve Backseat Test - Backseating A Valve | ZECO Valve<\/title>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/zecovalve.com\/fr\/spotlight-back-seating-on-api600-wedge-gate-valves-zeco.html\" \/>\n<meta property=\"og:locale\" content=\"fr_FR\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"Gate Valve Backseat Test - Backseating A Valve | ZECO Valve\" \/>\n<meta property=\"og:description\" content=\"What is a Backseat? A backseat is a seating arrangement inside the bonnet. It provides a seal between the stem and bonnet ... Lire plus\" \/>\n<meta property=\"og:url\" content=\"https:\/\/zecovalve.com\/fr\/spotlight-back-seating-on-api600-wedge-gate-valves-zeco.html\" \/>\n<meta property=\"og:site_name\" content=\"ZECO Valve\" \/>\n<meta property=\"article:published_time\" content=\"2021-12-28T08:50:17+00:00\" \/>\n<meta property=\"article:modified_time\" content=\"2022-10-17T12:57:43+00:00\" \/>\n<meta property=\"og:image\" content=\"https:\/\/zecovalve.com\/wp-content\/uploads\/2022\/06\/wedge-gate-valve-4.jpg\" \/>\n\t<meta property=\"og:image:width\" content=\"800\" \/>\n\t<meta property=\"og:image:height\" content=\"600\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<meta name=\"twitter:label1\" content=\"\u00c9crit par\">\n\t<meta name=\"twitter:data1\" content=\"Jerry\">\n\t<meta name=\"twitter:label2\" content=\"Dur\u00e9e de lecture estim\u00e9e\">\n\t<meta name=\"twitter:data2\" content=\"2 minutes\">\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\/\/schema.org\",\"@graph\":[{\"@type\":\"WebSite\",\"@id\":\"https:\/\/zecovalve.com\/#website\",\"url\":\"https:\/\/zecovalve.com\/\",\"name\":\"ZECO Valve\",\"description\":\"Industrial Ball Valve, Gate Valve and Globe Valve Manufacturer\",\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":\"https:\/\/zecovalve.com\/?s={search_term_string}\",\"query-input\":\"required name=search_term_string\"}],\"inLanguage\":\"fr-FR\"},{\"@type\":\"ImageObject\",\"@id\":\"https:\/\/zecovalve.com\/spotlight-back-seating-on-api600-wedge-gate-valves-zeco.html#primaryimage\",\"inLanguage\":\"fr-FR\",\"url\":\"https:\/\/zecovalve.com\/wp-content\/uploads\/2022\/06\/wedge-gate-valve-4.jpg\",\"width\":800,\"height\":600,\"caption\":\"GATE VALVE\"},{\"@type\":\"WebPage\",\"@id\":\"https:\/\/zecovalve.com\/spotlight-back-seating-on-api600-wedge-gate-valves-zeco.html#webpage\",\"url\":\"https:\/\/zecovalve.com\/spotlight-back-seating-on-api600-wedge-gate-valves-zeco.html\",\"name\":\"Gate Valve Backseat Test - Backseating A Valve | ZECO Valve\",\"isPartOf\":{\"@id\":\"https:\/\/zecovalve.com\/#website\"},\"primaryImageOfPage\":{\"@id\":\"https:\/\/zecovalve.com\/spotlight-back-seating-on-api600-wedge-gate-valves-zeco.html#primaryimage\"},\"datePublished\":\"2021-12-28T08:50:17+00:00\",\"dateModified\":\"2022-10-17T12:57:43+00:00\",\"author\":{\"@id\":\"https:\/\/zecovalve.com\/#\/schema\/person\/f65555145e0ef282ff87649309aba6a3\"},\"breadcrumb\":{\"@id\":\"https:\/\/zecovalve.com\/spotlight-back-seating-on-api600-wedge-gate-valves-zeco.html#breadcrumb\"},\"inLanguage\":\"fr-FR\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\/\/zecovalve.com\/spotlight-back-seating-on-api600-wedge-gate-valves-zeco.html\"]}]},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\/\/zecovalve.com\/spotlight-back-seating-on-api600-wedge-gate-valves-zeco.html#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"item\":{\"@type\":\"WebPage\",\"@id\":\"https:\/\/zecovalve.com\/\",\"url\":\"https:\/\/zecovalve.com\/\",\"name\":\"Home\"}},{\"@type\":\"ListItem\",\"position\":2,\"item\":{\"@type\":\"WebPage\",\"@id\":\"https:\/\/zecovalve.com\/spotlight-back-seating-on-api600-wedge-gate-valves-zeco.html\",\"url\":\"https:\/\/zecovalve.com\/spotlight-back-seating-on-api600-wedge-gate-valves-zeco.html\",\"name\":\"Gate Valve Backseat Test &#8211; Backseating A Valve\"}}]},{\"@type\":\"Person\",\"@id\":\"https:\/\/zecovalve.com\/#\/schema\/person\/f65555145e0ef282ff87649309aba6a3\",\"name\":\"Jerry\"}]}<\/script>\n<!-- \/ Yoast SEO Premium plugin. -->","_links":{"self":[{"href":"https:\/\/zecovalve.com\/fr\/wp-json\/wp\/v2\/posts\/1668","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/zecovalve.com\/fr\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/zecovalve.com\/fr\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/zecovalve.com\/fr\/wp-json\/wp\/v2\/users\/2"}],"replies":[{"embeddable":true,"href":"https:\/\/zecovalve.com\/fr\/wp-json\/wp\/v2\/comments?post=1668"}],"version-history":[{"count":0,"href":"https:\/\/zecovalve.com\/fr\/wp-json\/wp\/v2\/posts\/1668\/revisions"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/zecovalve.com\/fr\/wp-json\/wp\/v2\/media\/16097"}],"wp:attachment":[{"href":"https:\/\/zecovalve.com\/fr\/wp-json\/wp\/v2\/media?parent=1668"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/zecovalve.com\/fr\/wp-json\/wp\/v2\/categories?post=1668"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/zecovalve.com\/fr\/wp-json\/wp\/v2\/tags?post=1668"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}