PICV

Description

PICV

PICV

Features of Pressure Independent Control Valve

  • No external energy is required for automatic flow regulation;
  • Automatically adjust equipment or pipeline flow to meet the required design flow;
  • No need for balance debugging before the system runs;
  • Keep pipe flow constant.

PICV Working Principle

When the pressure difference control range is above, the valve tank is completely compressed, the cross-flow area is only the minimum design channel, and the flow rate changes with the pressure difference. When the pressure difference is within the control range, the valve tank moves with the pressure difference, thus changing the flow area and keeping the flow at the set value. Under the pressure differential control range, the valve is fully extended to reveal the maximum overcurrent area, and the flow rate changes with the pressure difference.

PICV Installation and Commissioning

Dynamic Balancing Valve Installation and Commissioning

This valve is mainly used for flow regulation and hydraulic balance. It can not be used as a shutoff valve because there is a certain amount of leakage when it is closed. For specific use, please consult Zeco Valve Group.

PICV Material and Standard

Size Range: 1/2″~2″
Pressure Rating: 10bar ~ 25bar

Face to Face Dimensions:EN 558-1, ASME B 16.10

Flange End Dimension: BS 21

Inspection and Test: ISO 5208 / EN 12226-2

Part Material Standard
Body CuZn39Pb1 / C37000 EN12167/ASTM B135
Bonnet CuZn39Pb1 / C37000 EN12167/ASTM B135
Trim CuZn39Pb1 / C37000 EN12167/ASTM B135
Measuring Port CuZn39Pb1 / C37000 EN12167/ASTM B135
O-Ring EPDM / NBR ISO 4633
Handwheel Nylon ISO 4633
For materials options not listed, consult factory.

Zeco manufactures valves in more than 50 different alloys.

Product Enquiry

en_USEnglish

Get a free quote

Contact Form Demo